3.3.4. Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned below
to protect service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case
of a short-circuit on the motor output.
Overcurrent protection:
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal
overcurrent protection that can be used for upstream overload protection (UL-applications excluded). See par. 4-18. Moreover, fuses or circuit breakers
can be used to provide the overcurrent protection in the installation. Overcurrent protection must always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000 A
Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the frequency converter.
FC 300
K25-K75
1K1-2K2
3K0-3K7
5K5-7K5
11K
15K-18K5
22K
30K
37K
1) Max. fuses - refer to national/international regulations to select an appropriate fuse size.
FC 300
K37-1K5
2K2-4K0
5K5-7K5
11K-18K
22K
30K
37K
45K
55K-75K
Max. fuse size
1)
10A
20A
32A
63A
80A
125A
160A
200A
250A
1)
Max. fuse size
10A
20A
32A
63A
80A
100A
125A
160A
250A
MG.33.AB.02 - VLT is a registered Danfoss trademark
3. How to Install
(symmetrical), 500 V maximum.
rms
Voltage
200-240 V
type gG
200-240 V
type gG
200-240 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type aR
380-500 V
type aR
380-500 V
type aR
Voltage
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type gG
380-500 V
type aR
380-500 V
type aR
3
Type
Type
27