Danfoss ADAP-KOOL AKD 102 Operating Instructions Manual page 70

Drive high power
Hide thumbs Also See for ADAP-KOOL AKD 102:
Table of Contents

Advertisement

6 How to Programme the Frequency Converter
1-22 Motor Voltage
Range:
400. V*
[10. - 1000. V]
1-23 Motor Frequency
Range:
50. Hz*
[20 - 1000 Hz]
NB!
This parameter cannot be adjusted while the motor is running.
6
1-24 Motor Current
Range:
7.20 A*
[0.10 - 10000.00 A]
NB!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range:
1420. RPM* [100 - 60000 RPM]
NB!
This parameter cannot be changed while the motor is running.
70
Function:
Enter the nominal motor voltage according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Select the motor frequency value from the motor nameplate data.For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par.4-13
Maximum Reference
and par.3-03
to the 87 Hz application.
Function:
Enter the nominal motor current value from the motor nameplate data. This data is used for cal-
culating motor torque, motor thermal protection etc.
Function:
Enter the nominal motor speed value from the motor nameplate data. This data is used for calcu-
lating automatic motor compensations.
MG.11.O1.02 - ADAP-KOOL
®