DMS Manual

Fuses

The DMS 300 should be used with suitable fusing as
per the co-ordination requirements of the circuit..
Max pre-fuses: DMS 300 meets Type 1 co-ordination
with properly rated HRC fuses.
Use type gG 25A, 415 VAC or equivalent HRC fuses.
Semiconductor fuses are required to meet
UL, C-UL Certification .
Semiconductor fuses listed below are manufactured
by Bussmann and should be ordered directly from
Bussmann or their local supplier.
Bussmann, High Speed fuse, Square body, Size 000,
660 V, 20 Amps rated - Part no: 170 M 1310
or
Bussmann, British style, BS88, Type CT, 690 V,
20 Amps rated - Part no: 20CT
MG.05.A2.02 - VLT is a registered Danfoss trademark