Alert Category
Critical - Redundant Power Supply
SNMP Trap ID
9
CIM Information
Prefix: PLAT ID: 0810
User Response
1. Power load may be handled by remaining power supply. The system will attempt to throttle to
avoid a power supply over-current condition. But a system shutdown may happen anyway if the
power load is too great.
2. Reduce the total power consumption by removing newly added or unused options like drives or
adaptors.
3. Use the IBM Power Configurator utility to determine current system power consumption. For
more information and to download the utility, go to http://www-03.ibm.com/systems/
bladecenter/resources/powerconfig.html.
4. Replace the power supply with higher rated power.
• 800b050a-1e81ffff : Non-redundant:Insufficient Resources for [RedundancySetElementName] has
asserted. (Fan Zone 1)
This message is for the use case when a Redundancy Set has transitioned to Non-redundant:Insufficient
Resources.
May also be shown as 800b050a1e81ffff or 0x800b050a1e81ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix: PLAT ID: 0810
User Response
1. Make sure that the connectors on fan n are not damaged.
2. Make sure that the fan n connectors on the system board are not damaged.
3. Make sure that the fans are correctly installed.
4. Reseat the fans.
5. Replace the fans. (n = fan number)
• 800b050a-1e82ffff : Non-redundant:Insufficient Resources for [RedundancySetElementName] has
asserted. (Fan Zone 2)
This message is for the use case when a Redundancy Set has transitioned to Non-redundant:Insufficient
Resources.
May also be shown as 800b050a1e82ffff or 0x800b050a1e82ffff
Appendix A. Integrated management module II (IMM2) error messages
407