Table 7- 12 Diagnostic Data - Siemens SITRANS FUP1010 Operating Instructions Manual

Ultrasonic flowmeters ip67
Hide thumbs Also See for SITRANS FUP1010:
Table of Contents

Advertisement

Functions
7.11 Reflexor
Table 7- 12
Low Limit
High Limit
Noise Level Set
Doppler Frequency (Hz)
% Deviation
Signal Peak-to-Peak mV
FFT s/sec
FFT Peak
Carrier Fx
112
Diagnostic Data
Application Information
Function / Explanation
High Pass Filter Setting
Low Pass Filter Setting
Noise Filter Setting
Average FFT Frequency
The width of Spectra is used to determine beam
penetration and calibration. The selection of
"Slurry" in Application Data is recommended for
flow rate indication accuracy when the %
Deviation is less than 25. For % Deviation above
35 the use of "Liquid" is recommended.
For applications that continuously have %
Deviation between 25 and 35 proper selection of
either Liquid or Slurry can be confirmed by
comparison to a known flow reference.
Peak-to-Peak demodulation signal amplitude.
The acceptable range is between 100 and 3200
mV during typical flow conditions. If less than 100
mV, check Sensor type used and mounting
configuration. If greater than 3200 mV, try in-line
mounting and/or "detune" Carrier Fx.
Number of FFTs per second
Peak FFT Amplitude
Transmit Frequency code
Operating Instructions, 03/2012, A5E02951522-02