Danfoss VLT 5000 Series Manual page 161

Synchronizing and positioning option onizing and positioning option
Hide thumbs Also See for VLT 5000 Series:
Table of Contents

Advertisement

O.ERR_87
SyncPos
No more space for variables
Meaning
When the SyncPos program is started the space
for the necessary variables is reserved dynamically.
This space is now no longer available.
Cause and tip
You may have selected a maximum number of
variables which is too high. Reduce the maximum
number in "SETTINGS" → "COMPILER" (Standard
= 92).
Or the memory available is occupied with pro-
grams or arrays. Delete the programs with
"CONTROLLER" → "PROGRAMS" → "DELETE
ALL"
or delete both the programs and arrays, i.e. by
deleting the entire memory with "CONTROLLER"
→ "MEMORY" → "DELETE EEPROM". . . . .
NB!
Remember to follow the recommendations
concerning saving programs and parameters before
deleting the EEPROM.
O.ERR_90
SyncPos
MEMORY locked
Meaning
The program memory is write-protected and
cannot be altered.
Tip
This means that autorecognition can neither be set
nor deleted and programs can neither be saved or
deleted. Equally, → "RAM SAVE" and →
"EEPROM DELETE" will not be executed.
O.ERR_xx
SyncPos
Internal error ##
Meaning
If such an error should occur, please contact your
dealer and report the error number displayed to
the technical service department.
MG.10.J4.02 – VLT is a registered Danfoss trade mark
®
VLT
5000 SyncPos option
I I I I I VLT software SyncPos messages
The VLT software SyncPos messages are arranged
in alphabetical order. Letters following a % sign
represent variables which can be used in plain text
at the corresponding locations.
I Compilation error ...
SyncPos
Compilation error(s): program not saved!
Meaning and tip
A file is always compiled first and then saved. If
you want to save the program, for example in the
menu "CONTROLLER" → → → → → "SAVE PROGRAM" and
a syntax error is found during compilation this
message will be displayed.
Start the "SYNTAX CHECK" in the menu
"DEVELOPMENT", correct the syntax error and
then save the program.
I Connection to ... already exists ...
SyncPos
Connection to %d already exists [%s] - change to
new Window?
Meaning
When opening a new window or when trying to
connect a window with a controller that is already
linked to a window.
Yes The controller is disconnected from the old
window and linked to the new window.
No The controller stays connected to the old
window, the new window is not linked to a
controller.
I Controller is executing a program ...
SyncPos
Controller is executing a program or command!
Meaning
When the controller is executing a command or
program it is not available for additional com-
mands. You have to → → → → → "BREAK" the new com-
mand and restart it once the previous command
has been completely executed.
161