42
HOME_OFFSET
HOME_OFFSET indicates an offset in the variance
of the zero point from the reference switch or index
pulse. After moving home, the drive is moved to
the actual position + HOME_OFFSET. At this point
the zero point is set, too. However, this value does
not influence the DEFORIGIN command.
Content
Zero point offset for machine zero point or index
AXH
qc
4 3
ERRCOND
ERRCOND determines the behavior in event of an
error as follows:
0 = Standard, i.e. drive moves in COASTING,
control loop is interrupted.
1 = like 0, but brake is activated, see O_BRAKE
(48)
2 = motor stop with max. deceleration (stop ramp),
subsequently standstill control
3 = like 2, brake is activated in addition, but only
after MOTOR STOP.
All other activities such as MOTOR OFF etc.
must be set in the ON_ERROR routine.
Content
Behavior in event of an error
0 ... 3
MG.10.J4.02 - VLT is a registered Danfoss trade mark
®
VLT
5000 SyncPos option
44
ENDSWMOD
ENDSWMOD indicates how the control resp. the
VLT should behave when a limit switch has been
reached.
Error behavior see ERRCOND (43)
Content
Behavior at limit switch

Parameter Group

AXI

Value range

0 - 1
0 = Trigger error
1 = Stop motor with max. deceleration
# 0
4 5
I_REFSWITCH determines which input of the
option card should serve as reference switch. It is
possible to react to a positive or negative edge,
using a positive or negative number. . . . .
Behavior after reaching see HOMETYPE (40).
Content
Input reference switch
AXI
1 ... 8
= Reaction to a positive edge on
input 1 ... 8
0
on input 1 ... 8
# 0
# 0
# 0
143