1 Alarms
1.5.1 Alarm description
165071
Rotor resistance (MD x138) illegal
Scan
Softkey "Calculate controller data (MSD only)"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The value 0 has been entered for the rotor resistance (MD 1138 and MD 2138).
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
165072
Moment of inertia (MD x117) illegal
Scan
Softkey "Calculate controller data"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The value 0 has been entered for the moment of inertia (MD 1117 and MD 2117).
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
165073
Maximum speed smaller than field weakening speed
Scan
Softkey "Calculate controller data (MSD only)"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The maximum speed (MD 1146 and MD 2146) is smaller than the field weakening speed (MD 1142 and MD 2142).
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
165074
Field weakening speed (MD x142) not allowed
Scan
Softkey "Calculate controller data (MSD only)"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The value 0 has been entered for the field weakening speed (MD 1142 and MD 2142).
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
165075
No-load current (MD 1118) not allowed
Scan
Softkey "Calculate controller data (FDD only)"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The value 0 has been entered for the no-load current.
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
165076
Ratio maximum current / no-load current illegal
Scan
Softkey "Calculate controller data (FDD only)"
Effect
The controller data have been calculated, the machine data concerned has been given a suitable default value.
Explanation
The ratio maximum current (MD 1104) no-load current (MD 1118) exceeds 900.
Remedy
If necessary, correct value and repeat function.
Note
Applies as from SW 5.4
1–178
Siemens AG 2001 All rights reserved 6FC5198–jAB40