Complete the following steps:
1. If system failed to boot successfully, DC cycle system.
2. If system boots to F1 setup, update the UEFI image and reset bank to primary (if required). If the
system boots without error, recovery is complete and no additional action is required.
3. If system fails to boot, or if the firmware update attempt fails, (trained service technician only)
replace the system board.
• S.51003 [S.51003]
Explanation: An uncorrectable memory error was detected in DIMM slot % on rank %. [S.51003] An
uncorrectable memory error was detected on processor % channel %. The failing DIMM within the
channel could not be determined. [S.51003] An uncorrectable memory error has been detected. Fatal
Memory Error Occurred
Severity
Error
User Response
Complete the following steps:
1. Check Lenovo support site for an applicable service bulletin or firmware update that applies to
this memory error.
2. If the node has recently been installed, moved, serviced, or upgraded, verify that the DIMM is
properly seated and visually verify that there is no foreign material in any DIMM connector on that
memory channel. If either of these conditions is found, correct and retry with the same DIMM.
(Note: Event Log may contain a recent 580A4 event denoting detected change in DIMM
population that could be related to this problem.)
3. If no problem is observed on the DIMM connectors and the problem persists, replace the DIMM
identified by LightPath and/or event log entry.
4. If problem re-occurs on the same DIMM connector, swap the other DIMMs on the same memory
channel across channels one at a time to a different memory channel or Processor. (check
service information for this product/Install guide for population requirements for sparing/paring
modes). If problem follows a moved DIMM to a different memory channel, replace that DIMM.
5. (Trained service technician only) Remove affected Processor and inspect Processor socket pins
for damaged or mis-aligned pins. If damage is found, or this is an upgrade Processor, replace the
system board. If there are multiple Processor's, swap Processor's to move affected Procesor to
another Processor socket and retry. If problem follows the affected Processor (or there is only
one Processor), replace the affected Processor.
6. (Trained technician only)If problem stays with the original DIMM connector, re-inspect DIMM
connector for foreign material and remove, if found. If connector is damaged, replace system
board
• S.51006 [S.51006]
Explanation: A memory mismatch has been detected. Please verify that the memory configuration is
valid. One or More Mismatched DIMMs Detected
Severity
Error
User Response
Complete the following steps:
1. Could follow an uncorrectable memory error or failed memory test. Check the log and service
that event first. DIMMs disabled by other errors or actions could cause this event.
2. Verify that the DIMMs are installed in the correct population sequence.
704
Lenovo NeXtScale nx360 M5 water-cooled technology tray Lenovo NeXtScale n1200 Enclosure Installation and Service Guide