Figure 84. Rear bulkhead bracket screws installation
Step 7.
Reinstall the cover (see "Replacing the cover" on page 142).
Step 8.
Slide the compute node into the rack.
Step 9.
Reconnect the power cords and any cables that you removed.
Step 10. Turn on the peripheral devices and the compute node.
Removing a copper water loop
Use this information to remove a copper water loop.
Attention:
• Copper water loop supports Intel Xeon E5-2600 v3 and v4 series.
• Water loop is to be installed only by trained technicians.
• Do not touch the microprocessor contacts; handle the microprocessor by the edges only. Contaminants
on the microprocessor contacts, such as oil from your skin, can cause connection failures between the
contacts and the socket.
• The pins on the sockets are fragile. Any damage to the pins might require replacing the system board.
Read the safety information in Safety and Installation guidelines.
If you are replacing a server component in the water-cooled technology tray, you need to remove the water-
cooled technology tray from the chassis enclosure and refer to the "Removing a water-cooled technology
tray from a chassis" on page 139 and "Installing a water-cooled technology tray in a chassis" on page 140
sections.