Lenovo NeXtScale nx360 M5 Installation And Service Manual page 725

Water-cooled technology tray; enclosure
Hide thumbs Also See for NeXtScale nx360 M5:
Table of Contents

Advertisement

User Response
Complete the following steps:
1. F1 Setup -> Save Settings.
2. Retry OOB configuration update.
• W.50001 [W.50001]
Explanation: A DIMM has been disabled due to an error detected during POST. DIMM Disabled
Severity
Info
User Response
Complete the following steps:
1. If the DIMM was disabled because of a memory fault, follow the procedure for that event.
2. If no memory fault is recorded in the logs and no DIMM connector error LEDs are lit, re-enable
the DIMM through the Setup utility or the Advanced Settings Utility (ASU).
3. If the problem persists, Power cycle the compute node from the management console.
4. Reset the IMM to default settings.
5. Reset UEFI to default settings.
6. Update IMM and UEFI firmware.
7. Swap/reseat the DIMM from the disabled slot with a matching DIMM. If the slot remains
disabled, (trained technician only) replace system board
• W.58001 [W.58001]
Explanation: The PFA Threshold limit (correctable error logging limit) has been exceeded on DIMM
number % at address %. MC5 Status contains % and MC5 Misc contains %. DIMM PFA Threshold
Exceeded
Severity
Error
User Response
Complete the following steps:
1. If the compute node has recently been installed, moved, serviced, or upgraded, verify that the
DIMM is properly seated and visually verify that there is no foreign material in any DIMM
connector on that memory channel. If either of these conditions is found, correct and retry with
the same DIMM. (Note: The event Log might contain a recent 580A4 event denoting detected
change in DIMM population that could be related to this problem.)
2. Check the Lenovo support site for an applicable firmware update that applies to this memory
error. The release notes will list the known problems the update addresses.
3. If the previous steps do not resolve the problem, at the next maintenance opportunity, swap the
DIMMs on the same memory channel one at a time to a different memory channel or Processor.
(check service information for this product/Install guide for population requirements for sparing/
paring modes). If PFA follows a moved DIMM to any DIMM connector on the different memory
channel, replace the moved DIMM.
4. If no problem is observed on the DIMM connectors and the problem persists, replace the DIMM
identified by LightPath and/or event log entry.
5. If problem re-occurs on the same DIMM connector, swap the other DIMMs on the same memory
channel across channels one at a time to a different memory channel or Processor. (check
service information for this product/Install guide for population requirements for sparing/paring
modes). If problem follows a moved DIMM to a different memory channel, replace that DIMM.
Appendix B. UEFI/POST diagnostic codes
711