Figure 42. Hose assembly movement
Step 15. Continue to each chassis from the top chassis to the bottom chassis by reaching into each chassis
Location C and Location D quick connects and allow for a steady stream of water to flow. There
should be minimal air present in the sight glass.
Note: Be sure to always close the valve on the blue hose before disconnecting it from one of the
chassis locations as you work your way down the rack.
Step 16. Once complete, go back to the front and connect the facility return hose to the rack return hose.
Fully open all connections on both the supply and return side. The manifold should be completely
filled.
136
Lenovo NeXtScale nx360 M5 water-cooled technology tray Lenovo NeXtScale n1200 Enclosure Installation and Service Guide