Setpoint Controller – Rate and Load Control
speed
sensor
PID 1 process value source - load (P402-01 = 2)
PID 2 process value source - rate (P402-02 = 1)

Setup and Tuning

Before proceeding, it would be beneficial to qualify and quantify the terms you will
encounter in the setup and tuning of the control system.
Proportional Control (Gain),
P
The
term on the BW500 adjusts the control output based on the difference between the
set point and the measured flow rate. A higher
and faster to react to changes or disturbances. If set too high, the BW500 becomes less
stable, and more susceptible to oscillations in the control output.
allowable input range:
typical operating range:
default value:
Page 74
Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05
belt scale
load
speed
P
P
term makes the BW500 more sensitive
0.000 to 2.000
0.300 to 0.600
0.400
motor
speed
controller
- rate
motor
speed
controller
- load
PID 1 control
output,
(P201-02 = 4)
PID 2
control output,
(P201-03 = 4)
PID 1 remote
setpoint - load
(P255-01 = 1)
PID 2 remote
setpoint - rate
(P255-02 = 1)