Siemens Milltronics BW500 Operating Lnstructions page 45

Hide thumbs Also See for Milltronics BW500:
Table of Contents

Advertisement

Press
Span Calibration Current Span
Setup test Press ENTER to Start
Press
Initial Span Calibration in progress
Current Reading
The duration of the Span calibration is dependent on speed (P014), length (P016), and
revolutions (P360) of the belt.
if
Span Count Too Low
Press CLEAR to continue
Calibration Complete Deviation
Press ENTER to accept value:
Press
Span Calibration. Current Span
Setup test. Press ENTER to Start
Accepting the Span returns to start of Span. A new Span can be performed, or enter RUN
mode. If calibrating with a test weight or test chain, remove it from the scale and store in
a secure place before returning to RUN mode.
The moisture meter is ignored during calibration. If the Inclinometer is used,
Note:
then calibration is adjusted based on incline angle.
7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS
the current span count
0
the span count being calculated while cali-
%
bration is in progress
####
signal from load cell too low, ensure proper test
weight or chain is applied during calibration
check for proper load cell wiring and ensure ship-
ping brackets have been removed.
the deviation from the previous span.
For an initial span, there is no previous
span count; hence the deviation is 0.
0.00
e.g. the new span count,
36790
if accepted.
e.g. the current span
36790
count
Page 39