P634
Communication Totalizer Resolution
Used to set the number of fixed decimal places for Total 1 and Total 2 for SmartLinx or
Modbus communication.
Entry:
P634 Index
Primary Index 1
Primary Index 2
With 3 decimal places set, the largest readable value is 2, 147, 483.638. With 2 decimal
places set, the largest readable value is 21, 474, 836.38. With 1 or 0 decimal places set, the
largest readable value is 100, 000, 000.
This parameter is only relevant if viewing the totalizer value using remote
Note:
communications, such as SmartLinx or Modbus.
P635
Verification Totalizer
Enables a dedicated internal totalizer that totals the amount of material conveyed during
a zero or span verification. It is used to verify the accuracy of the scale.
If a printer is connected to a port and the required programming is in order, a printout of
the activity is automatically done on completion of the verification process.
Entry:
0 = off, verification totalizer disabled
1 = do not total, verification totalizer is enabled, but main totalizers
2 = add total, verification totalizer is enabled as well as main totalizers
1)
Date and time are not available with the BW500/L
2)
Main totalizers consist of internal totalizers 1 and 2, and external totalizers
1 and 2.
7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS
Description
Total 1 for SmartLinx communication
Total 2 for SmartLinx communication
YYYY-MM-DD HH:MM:SS
Instrument ID#:
Start Total
(T1):
End Total
(T1):
Net Total
(T1):
f
# of decimal
Value
places
f
3
3
2
2
1
1
0
0
f
3
3
2
2
1
1
0
0
1)
2)
are disabled
2)
Page 137