P402
PID Process Value Source
Determines the source of the process value (P402 – 01 or – 02) for the corresponding PID
system (1 or 2)
The process value is the value that the controller is trying to match with the setpoint
f
(
= 1)
Enter:
f
1 = rate
2 = load
3 = mA input 1
4 = mA input 2
P405
Proportional Term
Sets the proportional term (P405-01 or -02) for the corresponding PID system (1 or 2)
f
(
= 0.400)
The proportional term is the proportional gain. A gain of 1 is equivalent to a proportional
band of 100%.
The proportional band is the range of deviation from the setpoint that corresponds to the
full range or the control output.
Enter the proportional term 0.000 to 2.000.
P406
Integral Term
Sets the integral term (P406-01 or -02) for the corresponding PID system (1 or 2) (
Enter the integral term 0.000 to 2.000.
P407
Derivative Term
Sets the derivative term (P407-01 or -02) for the corresponding PID system (1 or 2)
(f = 0.050)
Enter the derivative term 0.000 to 1.000.
P408
Feed Forward Term
Sets the feed forward term (P408-01 or -02) for the corresponding PID system (1 or 2)
f
(
= 0.300)
Enter the feed forward term 0.000 to 1.000.
P410
Manual Mode Output
Displays the percentage output value (P410-01 or -02) for the corresponding PID system (1
or 2).
When the PID system is in manual, this is the value output, providing bumpless transfer
when switching from manual to auto. When switching from auto to manual, this
parameter is loaded with the current controlled value.
Page 132
Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS
f
= 0.200)
7ML19985DK05