Disconnect Control - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 8: AUTOMATION

Disconnect control

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 306: Disconnect scheme logic, sheet 4 of 4
The disconnect control element contains the auxiliary logic for control of circuit breakers
required for SCADA and the front panel interface. The control function incorporates select-
before-operate functionality. Selection is required before a control action is permitted.
Selecting a device inhibits service to other clients. Selection is also inhibited if an operation
is in-progress. The logic permits interlocking to be bypassed if required.
Select the Settings > Automation > Disconnects > Disconnect Control menu item to
open the disconnect control configuration window.
DISCONNECTS
385