DISTURBANCE RECORDER

Disturbance recorder
462
Figure 386: Analog channel trigger logic
The disturbance recorder is designed to capture short duration events, such as faults at a
high resolution. Under normal operation, the disturbance recorder is continuously
capturing pre-fault data and storing this data in memory. When a trigger is received, the
disturbance recorder will capture the data during the period of the fault. Both the pre-fault
and fault data are stored as a record in non-volatile memory within the D90
The disturbance recorder captures the instantaneous values of all voltage and current
signals connected to the D90
channels, each of which can be used to trigger or re-trigger the disturbance recorder. A re-
trigger captures an additional record but with no pre-fault data. Triggered and re-triggered
records are merged into a single file, and the maximum number of re-triggers for a
particular fault is user-programmable.