GE D90 Plus Instruction Manual page 112

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

IEC 61850 COMMUNICATIONS
Configurable GOOSE transmission
104
GOOSE VLAN Priority
Range: 0 to 7 in steps of 1
Default: 4
This setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE
messages to have higher priority than other Ethernet data. This setting is required by IEC
61850.
GOOSE VLAN ID
Range: 0 to 4096 in steps of 1
Default: 0
This setting allows the selection of a specific VLAN ID for each GOOSE sending device.
This value can be left at its default if the feature is not required.
GOOSE ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
The configurable GOOSE settings allow the D90
of different datasets within IEC 61850 GOOSE messages. Up to eight different configurable
datasets can be configured and transmitted, allowing for the optimization of data transfer
between devices. This is useful for intercommunication between D90
from other manufacturers that support IEC 61850.
Items programmed for datasets 1 through 8 will have changes in their status transmitted
once per protection pass for digital data and every 250 ms for analogue data.
The integrity GOOSE message is sent at the pre-configured rate for all datasets, even if no
changes in the data items are detected.
The configurable GOOSE feature is recommended for applications that require GOOSE
Plus
data transfer between UR
GOOSE is recommended for applications that require GSSE data transfer between UR
series IEDs. IEC 61850 GOOSE messaging contains a number of configurable parameters,
all of which must be correct for successful data transfer. It is critical that the configured
datasets at the transmission and reception devices are an exact match in terms of data
structure, and that the GOOSE addresses and name strings match exactly. Manual
configuration is possible, but third-party substation configuration software may be used to
automate the process. The EnerVista UR
files and import IEC 61850 SCD files produced by a substation configurator.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Transmission > Tx Configurable GOOSE menu item to open the configurable GOOSE
transmission configuration window.
Plus
to be configured to transmit a number
-series IEDs and devices from other manufacturers. Fixed
Plus
Setup software can produce IEC 61850 ICD
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
IEDs and devices
Plus
-