Front Panel Indications - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

DISTURBANCE RECORDER

Front panel indications

464
The recorder has two storage modes: protected and automatic overwrite. When the
memory is filled, either no new records are written to memory (protected mode) or the
oldest record is overwritten (automatic overwrite mode).
The digital fault reporter summary screen provides an indication that the disturbance
recorder is ready to capture data and has memory available. In protected mode, the Ready
to Capture indication is green when all of the following conditions hold.
The disturbance recorder is enabled.
The block trigger input is not asserted.
Memory is available.
A record capture is not currently in progress.
Otherwise the indication is red. In automatic overwrite mode, the Ready to Capture
indication is green when all of the following conditions hold.
The disturbance recorder is enabled.
The block trigger input is not asserted.
A record capture is not currently in progress.
The Memory Available indication is green when less than 80% of the memory has been
filled. It is yellow when the amount of memory filled is between 80% and 99%, and it is red
if 100% of the memory is filled.
Figure 388: Digital fault reporter summary screen
The disturbance recorder screen shows the individual records stored on the device. This
screen also has an indication of any active triggers (red indication) for the disturbance
recorders. If a continuous trigger is permanently active, it will not fill the memory of the
recorder. After the first record is generated it is effectively disabled by the trigger logic;
however, its status will be displayed on this screen. The user can also force triggering of the
recorder from this screen.