TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
Activation range:
Impedance
Load for voltage supervision inputs
Acknowledgement time
Debounce time:
Permanent current
Closing current
Opening current
LO (low range)
Range:
HI (high range)
Range:
Consumption:
Interruptions:
Baudrate:
Media:
Operation temperature:
Storage temperature:
Humidity:
GEK-106465A
PRODUCT DESCRIPTION
Programmable from 1 up to 255 Vdc in steps of 1 V
> 100 kOhm
2 mA + V/100 kOhm
<1 m
1 to 50 ms in steps of 1 ms
16 A
60 A during 1 second
0.3 A with L/R = 40 ms at 125 Vdc
0.25 A with L/R = 40 ms at 250 Vdc
24 to 48 Vdc (from 24 Vdc – 15% to 48 Vdc + 20%)
110 to 250 Vdc (from 110 Vdc – 15% to 250 Vdc + 20%)
110 to 240 Vac (from 110 Vac – 15% to 240 Vac + 20%)
5 W typical
0.25 W more per each activated output.
Typical 100 ms, without unit reset.
125 kbits per second
Glass fiber optic multimode with ST connectors.
Maximum recommended length 1Km
3 wire cable connection
Maximum recommended length 500m
- 10°C to + 60°C
- 40°C to + 80°C
95% without condensing.
CIO Remote CAN Digital I/O Module
2.4.3.
2.4.5.

ENVIRONMENTAL CHARACTERISTICS

2.4.1.

INPUTS

2.4.2.

OUTPUTS

CONTROL POWER SUPPLY

2.4.4.

CAN BUS

11