CHAPTER 7: PROTECTION
Breaker flashover
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 259: Breaker configuration logic, sheet 4 of 4
The detection of breaker flashover is based on the following condition.
1.
Breaker open.
2.
Voltage drop measured from either side of the breaker during the flashover period.
3.
Voltage difference drop.
4.
Measured flashover current through the breaker.
Furthermore, the breaker flashover scheme is applicable for cases where either one or two
sets of three-phase voltages are available across the breaker.
CONTROL ELEMENTS
323