GE D90 Plus Instruction Manual page 38

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

SPECIFICATIONS
30
NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT
Directionality:........................................................ co-existing forward and reverse
Polarizing:............................................................... voltage
Polarizing voltage:.............................................. V_2
Operating current:.............................................. I_2
Level sensing (zero-sequence): .................... |I_0| – K × |I_1|
Level sensing (negative-sequence):...........|I_2| – K × |I_1|
Restraint, K: ........................................................... 0.000 to 0.500 in steps of 0.001
Characteristic angle:......................................... 0 to 90° in steps of 1
Limit angle: ............................................................ 40 to 90° in steps of 1, independent for forward and reverse
Angle accuracy:................................................... ±2°
Offset impedance:.............................................. 0.00 to 250.00 ohms in steps of 0.01
Pickup level:........................................................... 0.05 to 30.00 pu in steps of 0.01
Dropout level: ....................................................... <98%
Operation time:.................................................... <16 ms at 3 × pickup at 60 Hz
NEGATIVE-SEQUENCE INSTANTANEOUS OVERCURRENT
Pickup level:........................................................... 0.000 to 30.000 pu in steps of 0.001
Dropout level: ....................................................... <98% of pickup
Level accuracy at 0.1 to 2.0 × CT: ............... ±0.5% of reading or ±1% of rated (whichever is greater)
Level accuracy at >2.0 × CT:.......................... ±1.5% of reading
Overreach: ............................................................. <2%
Pickup delay:......................................................... 0.00 to 600.00 seconds in steps of 0.01
Reset delay: ........................................................... 0.00 to 600.00 seconds in steps of 0.01
Operate time:........................................................ <20 ms at 3 × pickup at 60 Hz
Timing accuracy for operation at 1.5 ×
pickup: ................................................................ ±3% or ±4 ms (whichever is greater)
NEGATIVE-SEQUENCE OVERVOLTAGE
Pickup level:........................................................... 0.000 to 1.250 pu in steps of 0.001
Dropout level: ....................................................... <98% of pickup
Level accuracy:.................................................... ±0.5% of reading from 10 to 208 V
Pickup delay:......................................................... 0.00 to 600.00 seconds in steps of 0.01
Reset delay: ........................................................... 0.00 to 600.00 seconds in steps of 0.01
Timing accuracy: ................................................ ±3% or ±20 ms, whichever is greater
Operate time:........................................................ < 30 ms at 1.10 × pickup at 60 Hz
NEGATIVE-SEQUENCE TIME OVERCURRENT
Pickup level:........................................................... 0.000 to 30.000 pu in steps of 0.001
Dropout level: ....................................................... <98% of pickup
Level accuracy at 0.1 to 2.0 × CT: ............... ±0.5% of reading or ±1% of rated (whichever is greater)
Level accuracy at >2.0 × CT:.......................... ±1.5% of reading
Curve shapes:....................................................... IEEE Moderately Inverse, IEEE Very Inverse, IEEE Extremely
Curve multiplier:.................................................. 0.01 to 600.00 in steps of 0.01
Reset type: ............................................................. instantaneous/timed (per IEEE) and linear
Timing accuracy for 1.03 to 20 × pickup: ±3.5% of operating time or ±1 cycle (whichever is greater)
Inverse, IEC (BS) A, IEC (BS) B, IEC (BS) C, IEC Short Inverse, IAC
Inverse, IAC Short Inverse, IAC Very Inverse, IAC Extremely
2
Inverse, I
t, FlexCurves™ (programmable), definite time (0.01
second base curve)
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION

Advertisement

Table of Contents
loading