Equipment Manager Operands - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

SHARED OPERANDS

Equipment manager operands

444
Figure 371: Shared operands configuration window
The left side of this screen displays all D90
equipment manager function as shared operands. Select any operands from the other five
primary features by clicking on the >> button. Operands may be de-assigned as shared
operands by pressing the << button.
The following equipment manager operands are available for the D90
alphabetically by operand syntax.
Battery monitor operands
BAT MON AC FAIL DPO.............................Asserted when the AC supply failure monitor drops out.
BAT MON AC FAIL OP................................Asserted when the AC supply failure monitor operates.
BAT MON AC FAIL PKP..............................Asserted when the AC supply failure monitor picks up.
BAT MON CHG FAIL DPO.........................Asserted when the battery charger failure monitor drops out.
BAT MON CHG FAIL OP ............................Asserted when the battery charger failure monitor operates.
BAT MON CHG FAIL PKP..........................Asserted when the battery charger failure monitor picks up.
BAT MON DC GND DPO...........................Asserted when the DC ground fault monitor drops out.
BAT MON DC GND OP...............................Asserted when the DC ground fault monitor operates.
BAT MON DC GND PKP ............................Asserted when the DC ground fault monitor picks up.
BAT MON DC TRIP DPO............................Asserted when the DC distribution breaker monitor drops out.
BAT MON DC TRIP OP ...............................Asserted when the DC distribution breaker monitor operates.
BAT MON DC TRIP PKP.............................Asserted when the DC distribution breaker monitor picks up.
BAT MON HIGH VDC DPO.......................Asserted when the battery high DC voltage monitor drops out.
BAT MON HIGH VDC OP ..........................Asserted when the battery high DC voltage monitor operates.
Plus
operands that are available to the
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 9: EQUIPMENT MANAGER