Chapter 13: Security

Password security

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Plus
Line Distance Protection System

Security

This section describes how to program the D90
It is recommended that passwords be programmed for each security level and assigned to
specific personnel. There are two user password security access levels: command and
setting.
The command access level restricts the user from making any settings changes, but allows
the user to perform the following operations.
Operate breakers via the front panel interface.
Change the state of virtual inputs.
Clear event records.
Clear oscillography records.
Clear fault reports.
Change the system date and time.
Clear energy records.
Operate control pushbuttons.
The setting access level allows the user to make any changes to any of the setting values
and operate in test mode.
The command and setting passwords are not programmed when the device is shipped
from the factory. When a command or setting password is set to null, the password
security feature is disabled.
Plus
The D90
supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface.
This includes both keypad entry and the faceplate serial USB connection. Remote access is
defined as any access to settings or commands via any rear Ethernet port. Any changes to
the local or remote passwords enables this functionality.
The RS485 port can be configured as a either a local or remote connection through the
serial port
Connection
Plus
setting.
security features.