IEC 61850 COMMUNICATIONS

Logical node prefixes

116
The IEC 61850 logical node name prefix settings are used to create name prefixes to
uniquely identify each logical node. For example, the logical node "PTOC1" may have the
name prefix "abc". The full logical node name will then be "abcMMXU1". Valid characters
for the logical node name prefixes are upper and lowercase letters, numbers, and the
underscore (_) character, and the first character in the prefix must be a letter. This
conforms to the IEC 61850 standard.
Additional details regarding the logical node naming rules are provided in IEC 61850 parts
6 and 7-2. It is recommended that a consistent naming convention be used for an entire
substation project.
Select the Settings > Communications > IEC 61850 > Logical Node Prefixes menu item to
open the IEC 61850 logical node prefixes configuration window.
Figure 89: IEC 61850 logical node prefix configuration settings
The following IEC 61850 logical node name prefix settings are available for the UR
series.
CILO1 LN Prefix through CILO8 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for the interlocking logical nodes 1 through 368.
CSWI1 LN Prefix through CSWI8 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for the switch controller logical nodes 1 through 368.
GGIO1 LN Prefix through GGIO4 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for generic input and output logical nodes 1 through
4.
LPHD1 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for the physical device information logical nodes.