CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 145: Load encroachment characteristic
The element operates if the positive-sequence voltage is above a user-specified level and
asserts its output signal that can be used to block selected protection elements such as
distance or phase overcurrent. The following figure shows an effect of the load
encroachment characteristics used to block the quadrilateral distance element.
Figure 146: Load encroachment applied to distance element
Select the Settings > Protection > Elements > Group 1 > Load Encroachment menu item
to open the load encroachment configuration window.
GROUPED PROTECTION ELEMENTS
185