CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 123: Quadrilateral distance characteristic sample shapes
Transformer Voltage Connection
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3, Yd5, Yd7, Yd9, Yd11
Default: None
The phase distance elements can be applied to look through a three-phase delta-wye or
wye-delta power transformer. In addition, VTs and CTs could be located independently
from one another at different windings of the transformer. If the potential source is
located at the correct side of the transformer, this setting shall be set to "None".
This setting specifies the location of the voltage source with respect to the involved
power transformer in the direction of the zone. The following figure illustrates the usage
of this setting. In section (a), zone 1 is looking through a transformer from the delta into
the wye winding. Therefore, the zone 1
set to "Dy11". In section (b), zone 4 is looking through a transformer from the wye into the
delta winding. Therefore, the zone 4
to "Yd1". The zone is restricted by the potential point (location of the VTs) as illustrated in
section (d).
GROUPED PROTECTION ELEMENTS
Transformer Voltage Connection
Transformer Voltage Connection
setting shall be
setting shall be set