GE D90 Plus Instruction Manual page 279

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
set relatively short, but long enough to ride through the transition period of loss-of-
guard with the receipt of a permissive signal that occurs with a normal trip. Typical
setting values are from 4 to 32 ms. For most cases, a value of 8 ms may be used.
The tripping or unblocking window for loss-of-guard without permission is the difference
between the timers specified by the
delay settings. For the default settings, this difference is 150 – 8 = 142 ms and occurs
8 ms after loss-of-guard was received, when the timer specified by this setting has timed
out. During this interval, the scheme has permission to operate if a forward fault is
sensed, and no reverse faults or transient blocking.
Guard Healthy Reset Delay
Range: 0.000 to 65.535 seconds in steps of 0.001
Default: 0.015 seconds
This setting specifies the guard healthy security time delay. This is the time after the
channel is restored that the guard signal must be present before the directional
comparison unblocking scheme is put back in service. This reset timer allows the
scheme to ride through any chattering in the channel. Typical values are from 100 to
500 ms, with a value of 150 ms commonly used.
Loss of Guard Trip Window
Range: 0.000 to 65.535 seconds in steps of 0.001
Default: 0.015 seconds
This setting specifies the directional comparison unblocking lockout time delay. This is
the amount of time from when any loss-of-guard signal is received until the directional
comparison unblocking scheme is locked out without the presence of any RX1 to RX4
receive signal or any forward element. This timer seals-in when it expires, creating a
blocking signal for all scheme functions and disabling the scheme until the guard signal
is restored and the timer specified by the
Typical values for this setting are from 160 to 180 ms; for most cases, a setting of about
150 ms may be used.
Seal-In Delay
Range: 0.000 to 65.535 seconds in steps of 0.001
Default: 0.010 seconds
The
output operand is produced according to the directional comparison
DCUB OP
unblocking scheme logic. This setting specifies a minimum guaranteed duration for the
pulse. As this operand runs the trip table of the directional comparison
DCUB OP
unblocking scheme, the
operands are sealed-in for the same period of time.
Communication Bits
Range: 1, 2, 4
Default: 1
This setting specifies the number of bits available on the communications channel for
the scheme. With only one bit available, the scheme sends the direct under-reaching
transfer trip command on bit 1 (via the
command received on bit 1 (
identification provided by the phase selector to assert the
C, and
output operands.
TRIP
DCUB TRIP 3P
Loss of Guard Trip Window
Guard Healthy Reset Delay
DCUB TRIP
A,
DCUB TRIP
B,
DCUB TRIP
operand) and responds to the direct trip
DCUB TX1
RX1
setting). The scheme uses only local fault type
CONTROL ELEMENTS
and
Loss of Guard Pickup
setting expires.
C, and
trip
DCUB TRIP 3P
DCUB TRIP
A,
DCUB TRIP
B,
DCUB
271

Advertisement

Table of Contents
loading

Table of Contents