Vt Fuse Failure - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CONTROL ELEMENTS

VT fuse failure

284
Dropout Delay
Range: 0.000 to 60.000 seconds in steps of 0.001
Default: 0.000 seconds
This setting specifies the delay by which to extend the FlexMatrix dropout.
Latching
Range: Enabled, Disabled
Default: Disabled
When this setting is enabled, the FlexMatrix output is latched until the reset input is
asserted.
Reset
Range: any FlexLogic™ operand or shared operand
Default: OFF
Assertion of the operand assigned to this setting resets the FlexMatrix output when
latching is enabled.
Events
Range: Enabled, Disabled
Default: Enabled
This setting enables and disables the logging of FlexMatrix events in the sequence of
events recorder.
The logic is shown below for FlexMatrix 1. The logic is identical for all eight FlexMatrix
elements.
Every signal source includes a fuse failure scheme.
Figure 220: FlexMatrix scheme logic
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION

Advertisement

Table of Contents
loading

Table of Contents