GROUPED PROTECTION ELEMENTS
NOTE:
Phase undervoltage
224
Figure 175: Inverse time undervoltage curves
At 0% of pickup, the operating time is equivalent to the undervoltage delay setting.
The phase undervoltage element may be used to give a desired time delay operating
characteristic versus the applied fundamental voltage (phase-to-ground or phase-to-
phase for wye VT connections, or phase-to-phase for delta VT connections) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the
dropout voltage.
Select the Settings > Protection > Elements > Group 1 > Voltage > Phase UV menu item
to open the phase undervoltage configuration window.
Figure 176: Phase undervoltage configuration settings
The following settings are available for each phase undervoltage element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phase undervoltage protection element.
Signal Source
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting selects the signal source for the phase undervoltage protection element.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION