CHAPTER 6: COMMUNICATIONS
NOTE:

IEC 61850 actual values

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Bit 9: segmentation.
BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0
This setting specifies the buffer time.
TrgOps
Range: 0 to 65535 in steps of 1
Default: 0
This setting specifies a bitmask that selects the trigger options. The following bits are
Plus
supported by the D90
Bit 1: data-change.
Bit 4: integrity.
Bit 5: general interrogation.
IntgPd
Range: 0, or 250 to 4294967295 in steps of 1
Default: 0
This setting specifies the integrity period.
Please disconnect any IEC 61850 client connection to the D90
changes to the report configuration. Disconnecting the rear Ethernet connection from the
Plus
D90
will disconnect the IEC 61850 client connection.
Select the Actual Values > Communications > Communication menu item to open the
communications actual values window.
The following actual value is related to the IEC 61850 communications feature.
IEC 61850 Available
Range: Yes, No
This actual value indicates whether the IEC 61850 communications feature is available.
.
Figure 95: IEC 61850 actual values
IEC 61850 COMMUNICATIONS
Plus
prior to making setting
125