CHAPTER 6: COMMUNICATIONS
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
defined by the user selection of the FlexLogic™ operand whose state is represented in the
GSSE/GOOSE message. A user must program a DNA point from the appropriate FlexLogic™
operand.
Table 4: IEC 61850 DNA Assignments
DNA
IEC 61850 definition
1
Test
2
ConfRev
Remote input 1 must be programmed to replicate the logic state of a specific signal from a
specific remote device for local use. This programming is performed via the three settings
indicated below.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Inputs/Outputs > Remote Inputs menu item to open the remote inputs configuration
window.
Figure 83: Remote inputs configuration settings
The following settings are available for each of the 32 remote inputs.
Name
Range: up to 12 alphanumeric characters
Default: Rem Ip 1
This setting allows the user to assign descriptive text to the remote input.
Device
Range: 1 to 32 inclusive
Default: Remote Device 1
This setting selects the number (1 to 32) of the remote device which originates the
required signal, as previously assigned to the remote device via the
setting.
Bit Pair
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32, Config Item 1 to Config Item 64
Default: None
This setting selects the specific bits of the GSSE/GOOSE message required.
IEC 61850 COMMUNICATIONS
FlexLogic™ operand
IEC 61850 TEST MODE
IEC 61850 CONF REV
Remote Device 1 ID
109