CHAPTER 5: ENERVISTA SOFTWARE SUITE
Online traceability information
Additional traceability rules
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
This information is also available in printed settings file reports as shown in the example
below.
Figure 57: Settings file report showing traceability data
Plus
The D90
serial number and file transfer date are available for an online device through
actual values. Select the Actual Values > Product Information > Model Information menu
item within the EnerVista UR
Figure 58: Traceability data in actual values window
The following additional rules apply for the traceability feature.
If the user changes any settings within the settings file in the offline window, then the
traceability information is removed from the settings file.
If the user creates a new settings file, then no traceability information is included in
the settings file.
If the user converts an existing settings file to another revision, then any existing
traceability information is removed from the settings file.
If the user duplicates an existing settings file, then any traceability information is
transferred to the duplicate settings file.
EXTENDED ENERVISTA UR
Plus
Setup online window as shown in the example below.