CHAPTER 7: PROTECTION
Terminal one-pole open
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 245: Terminal three-pole open logic
The autoreclose scheme also has dedicated logic to determine if one pole is opened at the
local terminal. For single breaker operation, the
operand is used to derive this signal. For the 1&2 sequence, both breakers must
OPEN
either declare one pole open or be open or out-of-service. For the 1-2 sequence, breaker 1
must declare one pole open and breaker 2 must declare one pole open or be open or out-
of-service. For the 2-1 sequence, breaker 2 must declare one pole open and breaker 1
must declare one pole open or be open or out-of-service. Alternately, a user-defined
setting is available to generate this signal.
CONTROL ELEMENTS
or
BREAKER 1 ONE P OPEN
BREAKER 2 ONE P
303