CHAPTER 6: COMMUNICATIONS
Remote outputs: DNA bit pairs
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 84: Remote double-point status inputs configuration settings
The following settings are available for each of the 16 remote double-point status inputs.
Name
Range: up to 20 alphanumeric characters
Default: RemDPS Ip 1
This setting specifies specific an exact identification (ID) for each remote double-point
status input.
Device
Range: Remote Device 1 through Remote Device 32
Default: Remote Device 1
This setting selects a remote device ID to indicate the origin of a GOOSE message.
Item
Range: None, Dataset Item 1 through Dataset Item 64
Default: None
This setting specifies the required bits of the GOOSE message.
Default State
Range: Intermediate, Off, On, Bad, Latest
Default: Latest
This setting selects the default value for the offline remote double-point status input.
Events
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the logging of remote double-point status input events
in the sequence of events recorder.
Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages
that are transmitted to remote devices on a LAN. Each digital point in the message must
be programmed to carry the state of a specific FlexLogic™ operand. The above operand
setting represents a specific DNA function (as shown in the following table) to be
transmitted.
IEC 61850 COMMUNICATIONS
111