LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 219: FlexMatrix configuration settings
The following settings are available for each of the eight FlexMatrix elements.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables or disables the FlexMatrix element.
Name
Range: 12 alphanumeric characters
Default: Flexmat 1
This setting specifies the name associated with a particular FlexMatrix element.
Input 1 Enable, Input 2 Enable,..., Input 16 Enable
Range: Enabled, Disabled
Default: Disabled
These settings enabled and disabled the 16 FlexMatrix inputs for each FlexMatrix. These
inputs can be assigned FlexLogic™ operands or shared operands, which can then be
assigned to any or all of the FlexMatrix outputs.
Block
Range: any FlexLogic™ operand or shared operand
Default: OFF
Assertion of the operand assigned to this setting blocks operation of the FlexMatrix
element.
Pickup Delay
Range: 0.000 to 60.000 seconds in steps of 0.001
Default: 0.000 seconds
This setting specifies the delay by which to extend the FlexMatrix pickup.
CONTROL ELEMENTS
283