Protection Virtual Outputs - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION

Protection virtual outputs

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 273: Protection virtual input logic
There are 96 virtual outputs that may be assigned via FlexLogic™. Virtual outputs are
resolved in each pass through the evaluation of FlexLogic™ equations.
Select the Settings > Protection > Protection Inputs/Outputs > Virtual Outputs menu
item to access the protection virtual output configuration settings.
Figure 274: Protection virtual output settings
The following settings are available for each protection virtual output. If not assigned, the
virtual output will be forced to off (logic 0).
ID
Range: up to 12 alphanumeric characters
Default: Virt Op 1
This setting specifies an identifier that may be assigned to each protection virtual
output.
Events
Range: Enabled, Disabled
Default: Disabled
If this setting is "Enabled", every change in the protection virtual output state will trigger
an event in the sequence of events recorder.
PROTECTION INPUTS AND OUTPUTS
337