Ggio2 Control Configuration - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 6: COMMUNICATIONS

GGIO2 control configuration

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
generally be used for SOE logs since the buffering capability reduces the chances of
missing data state changes. Unbuffered reporting should generally be used for local status
display.
Select the Settings > Communications > IEC 61850 > GGIO1 Status Configuration menu
item to open the GGIO1 status configuration window.
Figure 91: IEC 61850 GGIO1 status configuration
The following settings are available.
Number of Status Points
Range: 8 to 128 in steps of 8
Default: 8
This setting specifies the number of "Ind" points (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to this setting will not take effect until
Plus
the D90
is restarted.
GGIO1 Indication 1, GGIO1 Indication 2,..., GGIO1 Indication 128
Range: any logic operand
Default: OFF
These settings assign operands to represent GGIO1 status indications.
The GGIO2 logical node is available to provide access to the D90
inputs are single-point control (binary) values that can be written by clients. They are
generally used as control inputs. GGIO2 provides access to virtual inputs through the
IEC 61850 standard control model (ctlModel) services:
Status only
Direct control with normal security
SBO control with normal security
Configuration settings are available to select the control model for each point. Each virtual
input used through GGIO2 should be enabled and the corresponding SPSCO ctlModel
setting programmed to the appropriate control configuration.
Select the Settings > Communications > IEC 61850 > GGIO2 Control Configuration menu
item to open the GGIO2 control configuration window.
IEC 61850 COMMUNICATIONS
Plus
virtual inputs. Virtual
121