Safety Stop Function (Available Only For The Safety Stop Function Model) - Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual

Fr-e700 series
Table of Contents

Advertisement

2.3.4

Safety stop function (available only for the safety stop function model)

(1)
Description of the function
The terminals related to the safety stop function are shown below.
Terminal Symbol
S1
For input of safety stop channel 1.
∗1
For input of safety stop channel 2.
S2
∗1
Common terminal for terminal S1 and S2.
PC
∗1
Outputs the safety stop status
SAFE
The signal is output when inverter output is shut off due to the
FU
∗2
signal
safety stop function.
SAFE2
Outputs when an alarm or failure is detected.
RUN
∗3
The signal is output when no internal safety circuit failure
signal
SE
Common terminal for open collector outputs (terminal RUN and FU)
∗1
In the initial status, terminal S1 and S2 are shorted with terminal PC by shortening wire. Remove the shortening wire and connect the safety relay module
when using the safety stop function.
∗2
In the initial setting, output frequency detection (FU signal) is assigned to terminal FU. Set "80" to Pr.191 FU terminal function selection to assign SAFE signal.
The function can be assigned to other terminals by setting "80 (positive logic) or 180 (negative logic)" to any of Pr.190 to Pr.192 (Output terminal function
selection). (Refer to page 145)
∗3
In the initial setting, inverter running (RUN signal) is assigned to terminal RUN. Set "81" to Pr.190 RUN terminal function selection to assign SAFE2 signal. The
function can be assigned to other terminals by setting "81 (positive logic) or 181 (negative logic)" to any of Pr.190 to Pr.192 (Output terminal function selection).
(Refer to page 145)
∗4
At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.
.....
Specifications differ according to the date assembled. Refer to page 338 to check the SERIAL number.
NOTE
Hold the ON or OFF status for 2ms or longer to input signal to terminal S1 or S2. Signal input shorter than 2ms is not
recognized.
Use SAFE signal to monitor safety stop status. SAFE signal cannot be used as safety stop input signal to other
devices (other than the safety relay module).
SAFE 2 signal can only be used to output an alarm or to prevent restart of an inverter. The signal cannot be used as
safety stop input signal to other devices.
(2)
Wiring connection diagram
To prevent restart at fault occurrence, connect terminals RUN (SAFE 2 signal) and SE to terminals XS0 and XS1, which are
the feedback input terminals of the safety relay module.
By setting Pr. 190 RUN terminal function selection = "81 (SAFE2 signal)", terminal RUN is turned OFF at fault occurrence.
Emergency
stop button
+24V
X0
DC24V
24G
MITSUBISHI MELSEC Safety relay module
QS90SR2SN-Q
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 192 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
START/RESET
STOP
COM0
X1
COM1
XS0 XS1
Z00
Z10
K1
Internal
Safety
Circuit
K2
Z01
Z11
Control circuit specifications
Description
Between S1 and PC / S2 and PC
Open: In safety stop state.
Short: Other than safety stop state.
OFF: Drive enabled or drive stop (at an internal
safety circuit failure
ON: Drive stop (no internal safety circuit failure
OFF: Internal safety circuit failure
exists.
ON : No internal safety circuit failure
∗4
*1
FU(SAFE)
monitor
*1
RUN(SAFE2)
SE
STF
*2
STF
I/O control
*2
STR(STOP)
S1
Output shutoff
S2
circuit
PC
Z20
SD
Z21
*1 Output signals differ by the setting of Pr.190 and
Pr.191 (Output terminal function selection).
*2 Input signals differ by the setting of Pr178 to Pr.182
(Input terminal function selection).
)
∗4
∗4
∗4
R S T
Inverter
U V W
IM
)
∗4
2