6.1.5

Checking the inverter and converter modules

<Preparation>
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
(2) Prepare a tester. (Use 100Ω range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, P/+ and N/-, and check for
electric continuity.
NOTE
1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of electric discontinuity, the measured value is almost
continuity, due to the smoothing capacitor, the tester may not indicate
value is several to several tens-of ohms depending on the module type, circuit tester type, etc. If all measured
values are almost the same, the modules are without fault.
<Module device numbers and terminals to be checked>
Three-phase 200V class, Three-phase 400V class, Single-phase 200V class
Tester Polarity
Measured
R/L1
P/+
Discontinuity
D1
P/+
R/L1 Continuity
S/L2
P/+
Discontinuity
D2
P/+
S/L2 Continuity
T/L3∗
P/+
Discontinuity
D3∗
P/+
T/L3∗ Continuity
U
P/+
Discontinuity
TR1
P/+
U
Continuity
V
P/+
Discontinuity
TR3
P/+
V
Continuity
W
P/+
Discontinuity
TR5
P/+
W
Continuity
(Assumes the use of an analog meter.)
∗ T/L3, D3 and D6 are only for the three-phase power input models.
Single-phase 100V class
Tester Polarity
Measured
S/L2
P/+
Discontinuity
D1
P/+
S/L2 Continuity
S/L2
N/−
Continuity
D2
N/−
S/L2 Discontinuity
U
P/+
Discontinuity
TR1
P/+
U
Continuity
V
P/+
Discontinuity
TR3
P/+
V
Continuity
W
P/+
Discontinuity
TR5
P/+
W
Continuity
(Assumes the use of an analog meter.)
Tester Polarity
Value
R/L1
N/−
D4
N/−
R/L1 Discontinuity
S/L2
N/−
D5
N/−
S/L2 Discontinuity
T/L3∗
N/−
D6∗
N/−
T/L3∗ Discontinuity
U
N/−
TR4
N/−
U
V
N/−
TR6
N/−
V
W
N/−
TR2
N/−
W
Tester Polarity
Value
R/L1
P/+
Discontinuity
P/+
R/L1 Discontinuity
R/L1
N/−
Discontinuity
N/−
R/L1 Discontinuity
U
N/−
Continuity
TR4
N/−
U
Discontinuity
V
N/−
Continuity
TR6
N/−
V
Discontinuity
W
N/−
Continuity
TR2
N/−
W
Discontinuity
. When there is an instantaneous electric
. At the time of continuity, the measured
Measured
Value
Converter module
Continuity
D1
D2
Continuity
R/L1
Continuity
S/L2
Continuity
T/L3
Discontinuity
Continuity
Discontinuity
D4
D5
Continuity
Discontinuity
Measured
Value
Converter module
D1
R/L1
S/L2
D2
Inspection items
P/+
Inverter module
TR1
TR3
D3
C
D6
TR4
TR6
N/−
P/+
Inverter module
TR1
TR3
C
C
TR4
TR6
N/−
TR5
U
V
W
TR2
TR5
U
V
W
TR2
6