Operation
panel
indication
Name
Regenerative overvoltage trip during constant speed
If regenerative energy causes the inverter's internal main circuit DC voltage to
reach or exceed the specified value, the protective circuit is activated to stop
Description
the inverter output. The circuit may also be activated by a surge voltage
produced in the power supply system.
Check for sudden load change.
Check that the setting of Pr. 22 Stall prevention operation level is not too small.
Check point
Check if the stall prevention operation is frequently activated in an
Keep load stable.
Check that regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886)
Corrective
Use the brake resistor, brake unit or power regeneration common converter
action
Set the Pr.22 Stall prevention operation level correctly.
Set Pr.154 Voltage reduction selection during stall prevention operation = "11".
Operation
panel
indication
Name
Regenerative overvoltage trip during deceleration or stop
If regenerative energy causes the inverter's internal main circuit DC voltage to
reach or exceed the specified value, the protective circuit is activated to stop
Description
the inverter output. The circuit may also be activated by a surge voltage
produced in the power supply system.
Check for sudden speed reduction
Check point
Check if the stall prevention operation is frequently activated in an
Increase the deceleration time. (Set the deceleration time which matches the
Longer the brake cycle.
Corrective
Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886).
action
Use the brake resistor, brake unit or power regeneration common converter
Set Pr.154 Voltage reduction selection during stall prevention operation = "11".
E.OV2
application with a large load inertia.
is used.
(FR-CV) as required.
E.OV3
application with a large load inertia.
moment of inertia of the load)
(FR-CV) as required.
FR-PU04
FR-PU07
FR-PU04
FR-PU07
2/4
Stedy Spd OV
OV During Dec