4.11.5 Output terminal function selection (Pr. 190 to Pr. 192)

You can change the functions of the open collector output terminal and relay output terminal.
Parameter
Number
190
RUN terminal
function selection Open collector
191
FU terminal
function selection
192
A,B,C terminal
function selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 188)
∗1
The setting values "80, 81, 180 and 181" are available only in the safety stop function model.
∗2
The setting values "68 and 168" are only available for the safety stop function model with FR-E7DS mounted. (Refer to the Instruction Manual of FR-E7DS
for details.)
∗3
The setting values "93" and "193" are available only in Pr. 190 and Pr. 191.
.............. Specifications differ according to the date assembled. Refer to page 338 to check the SERIAL number.
(1)
Output signal list
You can set the functions of the output terminals.
Refer to the following table and set the parameters: (0 to 99: positive logic, 100 to 199: negative logic)
Setting
Signal
Positive
Negative
logic
logic
0
100
RUN
Inverter running
Up to frequency ∗1
1
101
SU
3
103
OL
Overload alarm
Output frequency
4
104
FU
detection
Regenerative brake
7
107
RBP
pre-alarm
Electronic thermal O/L
8
108
THP
relay pre-alarm
Inverter operation
11
111
RY
ready
Output current
12
112
Y12
detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward/reverse
16
116
RL
rotation output
20
120
BOF
Brake opening request
25
125
FAN
Fan fault output
Heatsink overheat
26
126
FIN
pre-alarm
During deceleration at
46
146
Y46
occurrence of power
failure
During PID control
47
147
PID
activated
Function assignment of external terminal and control
Initial
Name
Value
output terminal
Relay
output terminal
Function
Output during operation when the inverter output frequency
rises to or above Pr. 13 Starting frequency.
Output when the output frequency is reached to the set frequency. Pr. 41
Output while stall prevention function is activated.
Output when the output frequency reaches the frequency
set in Pr. 42 (Pr. 43 for reverse rotation).
Output when 85% of the regenerative brake duty set in Pr.
70 is reached.
Output when the electronic thermal value reaches 85% of
the trip level. (Electronic thermal relay function protection
(E.THT/E.THM) activates, when the value reached 100%.)
Output when reset process is completed (when the inverter
can be started by switching the start signal ON or while it is
running) after powering on inverter.
Output when the output current is higher than the Pr. 150
setting for longer than the time set in Pr. 151 .
Output when the output power is lower than the Pr. 152
setting for longer than the time set in Pr. 153 .
Output when the feedback value falls below the lower limit
of PID control.
Output when the feedback value rises above the upper limit
of PID control
Output when forward rotation is performed in PID control.
Output to open the brake when the brake sequence
function is selected.
Output at the time of a fan fault.
Output when the heatsink temperature reaches about 85%
of the heatsink overheat protection providing temperature.
Output when the power failure-time deceleration function is
executed.
(retained until release)
Output during PID control.
Initial Signal
0
RUN (inverter running)
FU (output frequency
4
detection)
99
ALM (fault output)
Operation
Setting Range
0, 1, 3, 4, 7, 8, 11 to 16, 20, 25,
*2
*1
*1
26, 46, 47, 64, 68
, 80
, 81
, 90,
*3
91, 93
, 95, 96, 98, 99, 100, 101,
103, 104, 107, 108, 111 to 116,
120, 125, 126, 146, 147, 164,
*2
*1
*1
168
, 180
, 181
, 190, 191,
*3
193
, 195, 196, 198, 199, 9999
Refer
Related
to
Parameter
Page
147
149
Pr. 22, Pr. 23,
92
Pr. 66
Pr. 42, Pr. 43
149
Pr. 70
130
Pr. 9, Pr. 51
116
147
Pr. 150,
150
Pr. 151
Pr. 152,
150
Pr. 153
Pr. 127 to
246
Pr. 134
Pr. 278 to
Pr. 283,
135
Pr. 292
Pr. 244
263
298
Pr. 261
168
Pr. 127 to
246
Pr. 134
145
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents