Pr. 14 = 2
For vertical lift loads
At forward rotation boost...Pr. 0 (Pr. 46)
setting
At reverse rotation boost...0%
100%
Forward
rotation
Reverse
Pr. 0
rotation
Pr. 46
Base frequency
Output frequency (Hz)
REMARKS
When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in Pr. 19 Base frequency voltage
to prevent trip due to current at regeneration.
In addition, when the RT signal is ON, the other second functions are also valid.
NOTE
Load pattern selection does not function under Advanced magnetic flux vector control and General-purpose
magnetic flux vector control.
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 0, Pr. 46 (Torque boost)
Pr. 3 Base frequency
Pr. 178 to Pr. 184 (input terminal function selection)
General-purpose magnetic flux vector control
Advanced magnetic flux vector control
Pr. 14 = 3
For vertical lift loads
At forward rotation boost...0%
At reverse rotation boost...Pr. 0 (Pr. 46)
100%
Reverse
rotation
Forward
Pr. 0
rotation
Pr. 46
Base frequency
Output frequency (Hz)
Refer to page 85
Refer to page 98
Refer to page 139
Refer to page 86
Refer to page 86
(3) Constant-torque
(setting "2, 3")
Set "2" when a vertical lift load is fixed as power
driving
load
setting
regenerative load at reverse rotation.
Pr. 0 Torque boost is valid during forward rotation
and torque boost is automatically changed to
"0%" during reverse rotation. Pr. 46 Second
torque boost is valid when the RT signal turns
ON.
Set "3" for an elevated load that is in the driving
mode during reverse rotation and in the
regenerative load mode during forward rotation
according to the load weight, e.g. counterweight
system.
For the RT signal, set "3" in any of Pr. 178 to Pr.
184 (input terminal function selection) to assign
the function.
V/F pattern
load
application
at
forward
rotation
and
101