Condition Selection Of Function Validity By Second Function Selection Signal (Rt) - Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual

Fr-e700 series
Table of Contents

Advertisement

Function assignment of external terminal and control
4.11.3

Condition selection of function validity by second function selection signal (RT)

You can select the second function using the RT signal.
When the RT signal turns ON, the second function becomes valid.
For the RT signal, set "3" in any of Pr. 178 to Pr. 184 (input terminal function selection) to assign the function.
The second function has the following applications.
(a) Switching between normal use and emergency use
(b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line acceleration/deceleration
(d) Switching of characteristic between the main motor and sub motor
Second function connection diagram
Start
Second function
selection
High speed
Middle speed
When the RT signal is ON, the following second function is selected at the same time.
Function
Torque boost
Base frequency
Acceleration time
Deceleration time
Electronic thermal O/L relay
Stall prevention
Applied motor
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 178 to Pr. 184 (input terminal function selection)
142
Inverter
STF(STR)
RT
RH
RM
SD
First Function
Parameter Number
Pr. 0
Pr. 3
Pr. 7
Pr. 8
Pr. 9
Pr. 22
Pr. 71
Second acceleration/deceleration time
RT
RH
RM
Second Function
Parameter Number
Pr. 46
Pr. 47
Pr. 44
Pr. 44, Pr. 45
Pr. 51
Pr. 48
Pr. 450
Refer to page 139
Acceleration time
is reflected
Refer to
Page
85
98
109
109
116
92
118
Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents