Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual page 212

Fr-e700 series
Table of Contents

Advertisement

Communication operation and setting
(2)
PU connector communication system configuration
Connection of a computer to the inverter (1:1 connection)
FR-PU07
RJ-45 connector 2)
Communication cable 1)
Combination of a computer and multiple inverters (1:n connection)
interface/terminals
RS-232C
∗ The inverters may be affected by reflection depending on the transmission speed or transmission distance. If this reflection hinders communication, provide a
terminating resistor. If the PU connector is used to make a connection, use a distributor since a terminating resistor cannot be fitted. Connect the terminating
resistor to only the inverter remotest from the computer. (Terminating resistor: 100Ω)
REMARKS
Refer to the following when fabricating the cable on the user side.
Examples of product available on the market (as of October 2008)
Product
1) Communication cable
2) RJ-45 connector
∗1 Do not use pins No. 2, 8 of the communication cable. (Refer to page 211)
212
Computer
Inverter
PU
RS-485
connector
interface/terminals
Station 0
Computer
Inverter
connector
RS-485
Distributor
Communication cable 1)
Computer
RS-232C
Connector
Station 1
Inverter
Maximum
cable
15m
connector
RS-232C
RS-485
converter
Distributor
Communication cable 1)
Type
SGLPEV-T (Cat5e/300m)
24AWG × 4P ∗1
5-554720-3
Station 0
Inverter
PU
RS-232C
connector
RJ-45
connector 2)
Communication cable 1)
Station 1
Inverter
PU
PU
connector
RJ-45 connector 2)
Station 2
Inverter
PU
PU
connector
RJ-45 connector 2)
Mitsubishi Cable Industries, Ltd.
Tyco Electronics Corporation
Station 0
Computer
Inverter
RS-232C
connector
Maximum
connector
cable
15m
RS-232C
RS-485
converter
Communication cable 1)
Station n
(max. 32 inverters)
Inverter
PU
connector
Terminating resistor *
Station n
Inverter
PU
connector
Terminating resistor *
Maker
PU
RJ-45
connector 2)

Hide quick links: