Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual Page 115

Fr-e700 series.
Hide thumbs

Advertisement

Setting of acceleration/deceleration time and acceleration/ deceleration pattern
(2)
Adjustment of shortest acceleration/deceleration mode (Pr. 61 to Pr. 63)
By setting the adjustment parameters Pr. 61 and Pr. 63, the application range can be made wider.
Parameter
Name
Number
61
Reference current
Reference value at
62
acceleration
Reference value at
63
deceleration
REMARKS
Since the Pr. 61 to Pr. 63 settings automatically return to the initial value (9999) if the Pr. 292 setting is changed, set Pr. 292 first
when you need to set Pr. 61 to Pr. 63.
Parameters referred to
Pr. 0 Torque boost
Pr. 7 Acceleration time, Pr. 8 Deceleration time
Pr. 22 Stall prevention operation level
Setting Range
0 to 500A
9999 (initial value)
0 to 200%
9999 (initial value)
Refer to page 85
Refer to page 109
Refer to page 92
Description
For example, when the motor and inverter are different in capacity,
set the rated motor current value.
Set reference current (A) of the stall prevention operation level
during acceleration/deceleration.
The rated inverter current is defined as reference.
Set when it is desired to change the reference level of acceleration
and deceleration.
Set the stall prevention operation level (ratio to the current value of
Pr. 61) during acceleration/deceleration.
Stall prevention operation level is 150% for the shortest acceleration/
deceleration.
4
115