Mitsubishi Electric FR-E720-0.1K(SC) Instruction Manual page 161

Fr-e700 series
Table of Contents

Advertisement

(2)
How to calibrate the terminal FM when using the operation panel
Operation
1.
Confirmation of the RUN indication and
operation mode indication
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Press
until
5.
Turn
until
Set to C0 FM terminal calibration.
6.
Press
to enable setting.
7.
If the inverter is at a stop, press the
to start the inverter.
(Motor needs not be connected.)
8.
Turn
to adjust the indicator needle to the
desired position.
9.
Press
.
Setting is complete.
Turn
Press
Press
REMARKS
Calibration can also be made for external operation. Set the frequency in the External operation mode, and make calibration in
the above procedure.
Calibration can be made even during operation.
For operation from the parameter unit (FR-PU04/FR-PU07), refer to the instruction manual of the parameter unit.
Parameters referred to
Pr. 54 FM terminal function selection
Pr. 55 Frequency monitoring reference
Pr. 56 Current monitoring reference
Monitor display and monitor output signal
appears.
appears.
appears.
key
Flicker...Parameter setting complete!!
to read another parameter.
to return to the
indication (step 4).
twice to show the next parameter (
Refer to page 154
Refer to page 159
Refer to page 159
Display
(When Pr. 54 = 1)
PRM indication is lit.
(The parameter number read previously appears.)
C0 to C7 setting
is enabled.
The monitor set to Pr. 54
FM terminal function selection
is displayed.
Analog indicator
).
4
161

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents