4.13 Advanced Drive Setup Adjustments
Predefined V/f Patterns for Models 2A0169 to 2A0396 and 4A0096 to 4A0590
The voltage values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.
Setting = 0
50 Hz
230
13.8
6.9
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
230
40.3
5.8
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
230
17.3
8.1
0
1.3 2.5
50
Frequency (Hz)
Setting = C
90 Hz
230
13.8
6.9
0
1.5 3
60
90
Frequency (Hz)
n
H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current
input.
No.
H3-01
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due
to gain and bias settings will be read as 0%.
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc without zero limit. If the resulting voltage is negative after being adjusted by gain and bias
settings, then the motor will rotate in reverse.
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings are limited to 0%.
176
Table 4.34 Rated Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
230
13.8
6.9
0
1.5 3
60
Frequency (Hz)
Table 4.35 Variable Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
230
57.5
6.9
0
1.3
25
50
Frequency (Hz)
Table 4.36 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
230
23
10.4
0
1.3 2.5
50
Frequency (Hz)
Table 4.37 Constant Output, Settings C to F
Setting = D
120 Hz
230
13.8
6.9
0
1.5 3
60
120
Frequency (Hz)
Name
Terminal A1 Signal Level Selection
Setting = 2
60 Hz
230
13.8
6.9
0
1.5 3
50
Frequency (Hz)
Setting = 6
60 Hz
230
40.3
5.8
0
1.5
30
Frequency (Hz)
Setting = A
60 Hz
230
17.3
8.1
0
1.5 3
Frequency (Hz)
Setting = E
180 Hz
230
13.8
6.9
0
1.5 3
60
Frequency (Hz)
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Setting = 3
230
13.8
6.9
60
0
1.5 3
Frequency (Hz)
Setting = 7
230
57.5
6.9
60
0
1.5
Frequency (Hz)
Setting = B
230
23
12.7
60
0
1.5 3
Frequency (Hz)
Setting = F
230
57.5
6.9
180
0
1.5 30
Frequency (Hz)
Setting Range
0 to 3
72 Hz
60
72
60 Hz
30
60
60 Hz
60
60 Hz
60
Default
0