S6: Z1000 Protection - YASKAWA Z1000 User Manual

Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
HAND Key Function
S5-07
Selection (HOA
(3235)
Keypad)
<1> Upper limit is 240.00 in drive software versions PRG: 1017 and earlier.
u

S6: Z1000 Protection

No.
(Addr.
Name
Hex)
S6-01
Emergency Override
(3236)
Speed
S6-02
Emergency Override
(3237)
Reference Selection
S6-03
ov2 Detect Time
(3238)
Main Contactor and
S6-04
Cooling Fan Power
(3239)
Supply Failure
Output Phase Loss
S6-07
Detection Level for
(323C)
Dynamic Audible Noise
Control
<1> Upper limit is 240.00 in drive software versions PRG: 1017 and earlier.
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
LCD Display
Determines whether the HAND key on the HOA keypad will be
Oper HAND Key
enabled for switching between HAND and AUTO.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
Sets the speed command used in Emergency Override mode when
S6-02 = 0.
E Override Speed
Selects the frequency reference source for the Emergency
Override function (H1-oo= AF or B0).
0: Use S6-01 Reference
1: Use AUTO Reference
E OverrideRefSel
Note:
0: Use S6-01 Ref
1: Use AUTO Ref
Sets the detection time of ov2 in 0.1 s increments.
ov2 Detect Time
Determines the action the drive should take when a fault occurs
FAN1 Fault Sel
with the external cooling fan.
0: Ramp to Stop
0: Ramp to stop
1: Coast to stop
1: Coast to Stop
2: Fast-Stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
Sets the output phase loss detection level for Dynamic Audible
Noise Control. Decrease the setting in steps of 10% when output
Outp Ph Loss Lv1
phase loss is detected erroneously. This setting rarely needs to be
changed.
Description
Description
In drive software versions PRG: 1013 and earlier,
if the CALL alarm is displayed, the Emergency
Override Forward (H1-0o = AF) and Emergency
Override Reverse (H1-0o = B0) inputs are
ignored. In drive software versions PRG: 1014 and
later, the Emergency Override inputs will function
even if the CALL alarm is displayed.
B.11 S: Special Application
Values
Page
Default: 1
Range: 0, 1
Values
Page
Default: 0.00
Hz
Min.: 0.00
Max.: [E1-04]
<1>
Default: 0
Range: 0, 1
Default: 10.0 s
Min.: 0.0
Max.: 1200.0
Default: 1
Range: 0 to 2
Default:
100.0%
Min.: 10.0
Max.: 100.0
B
329